Raypak 750 User Manual Page 5

  • Download
  • Add to my manuals
  • Print
  • Page
    / 10
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 4
Note: Current draw (Amps) is for pump only Water hardness grains per gallon
*Pump selections based on 75ft equivalent length of tubing Soft = 3-4 • Medium = 5-15 • Hard = 16-25
** At 230 VAC
Heater
Side
From Combustible
Surfaces (min.)
For Service
503/4A thru 2003/4A
For Service
2503 thru 4003
Floor* 0” 0” 0”
Rear 12” 24” 36”
Right Side 1” 1” 24”**
Left Side 1” 1” 24”**
Top Indoor
Outdoor
0”
Unobstructed
10”
Unobstructed
12”
Unobstructed
Front Open 24” 30”
Vent Stack Indoor 1” 1” 1”
Vent Cap Outdoor 12” 12” 12”
CLEARANCES
MVB
Model
Water Hardness
Soft Medium Hard
HP Amps HP Amps HP Amps
503A/504A 1/4 6 1/4 6 3/4 11
753A/754A 1/4 6 1/2 7 3/4 11
1003A/1104A 1/4 6 1/2 7 1 14
1253A 1/2 7 1 14 1 14
1503A/1504A 3/4 11 1 14 1 14
1753A 1 14 1-1/2 15 1-1/2 15
2003A/2004A 1-1/2 15 1-1/2 15 1-1/2 15
2503 1-1/2 8.2 1-1/2 8.2 3 16
3003 1-1/2 8.2 3 16 3 16
3503 1-1/2 8.2 3 16 3 16
4003 3 16 5 23 5 23
*Do not install on carpeting
Note: Local codes may require increased clearances
PUMP
5
All components are contained inside the
cabinet
(except PRV)
, no external fans or
valves to deal with.
RATING PLATE
2503 thru 4003
** One side 24” other 1” clearance.
Page view 4
1 2 3 4 5 6 7 8 9 10

Comments to this Manuals

No comments