Raypak’s Next Generation
Modulating Boiler
Time-honored technologies unite with cutting-edge advancements in
Raypak’s MVBmodulating vertical boiler. Never before has a vertical
boiler provided both the installer and building owner such installation
flexibility, ease-of-commissioning, reliability and long-term performance.
Small space, not a problem. The MVB 503A thru 2003A has the smallest
installed footprint of any vertical boiler, only 5.4 square feet. MVB mod-
els 2503 thru 4003 are just 11.7 square feet. Raypak’s MVB is built with
commercial-grade components and materials. From our structural steel
base to our stainless steel flue wrapper, you can tell the MVB is built to
last. It’s easy to handle and install, but still user friendly to service. Our
compact design fits through a 32” door opening making it the perfect
choice for those hard to reach retrofit projects. Now is the perfect time
to take a closer look at Raypak.
Flexibility
Small diameter vents and industry-leading vent length allowances
afford greater vent location options, thus reducing wasted space. Vent
versatility is further enhanced by the self-tuning combustion system
which compensates for unusual chimney and vent configurations.
Category I* -CSA-certified 84% boiler and up to 85% water heater
models available (504A-2004A). Our category I solution is the perfect
replacement for your retrofit applications. This reduces the installed
cost by using existing category I venting or chimney. Installation could-
n’t be easier; all connections are on the back of the unit. Start-up is a
snap, it’s as close to plug-n-play as a boiler can get.
Category IV -CSA-certified 87% thermal efficiency (503A-2003A) and
85% thermal efficiency (2503-4003) at full fire–the highest possible for
non-condensing boilers
(Up to 88.4% at part load!)
When the job
requires high efficiency, our category IV solution meets your needs.
At the heart of every Raypak MVB is a unique integral evaporator sys-
tem - the first defense against harmful condensation. Raypak’s evapora-
tor system collects and re-evaporates condensate which may form dur-
ing initial start-up or brief periods of cold-water operation, eliminating
the need for a boiler condensate drain. This saves you money on instal-
lation costs as well as the inconvenience of dealing with multiple con-
densate drains.
True Modulation
Modulation is nothing new to Raypak, we have honed our gas modula-
tion experience for over 65 years. The Raypak MVB will precisely track
the heating load with its built-in Versa IC
®
Integrated Control platform,
eliminating costly overshooting. Utilizing the latest technology for the
blower-gas valve package, the optimum fuel-air ratio is maintained
throughout the entire range of the load-tracking operation. Now with
up to 7:1 turndown (503A thru 4003 Cat IV) ensures efficiency is main-
tained throughout the firing rate and actually increases during part
load, right when you want it! The MVB automatically self-tunes to
accommodate the widest range of gas supply pressures. The high quali-
ty integrated blower-gas valve is self-correcting and allows smooth
operation with fluctuating gas supply pressures. The Raypak MVB is
cutting edge technology with atmospheric simplicity.
Key Features
16 models from 500,000 to 4,000,000 BTUH
Up to 85% efficiency (Cat. I*);
Up to 88.4% efficiency (Cat. IV)
No boiler condensate drain required (proprietary design)
Lowest minimum required inlet water temperature (120F)
Modulating gas valve and burner, up to 7:1 (503A thru 4003 Cat. IV)
turndown
Multiple pump outputs - Boiler, System, and Indirect DHW.
0-10 VDC BMS Interface (setpoint or direct drive).
Built-in cascade function for up to 4 boilers.
Built-in outdoor reset functionality.
Modbus BMS port.
Engineered with precisely matched system components
Small installed footprint design fits tight spaces and easily replaces
larger boilers
Advanced diagnostics center, real English fault codes
Indoor/outdoor construction
Complete cabinet protects all controls and wiring
Low NOx combustion system
Suitable for altitudes up to 10,000 ft. (derate above 5,000 ft.)
With all copper and bronze waterways (optional on some
models), the MVB is available in boiler and water heater configurations
Inline combustion air filter (MERV8)
All water heaters are low lead (<.25%) certified.
Category I*-up to 85% efficiency
Category IV-up to 88.4% efficiency
2
*Category I with vertical vent, category III with horizontal venting and no extractor.