CATEGORY I*
BOILERS
(TYPE H)
MVB
Model
Flow Rates Pressure Drops
Minimum Flow Maximum Flow 20°F 30°F 39°F
GPM
P FT T °F
GPM
P FT T °F
GPM
P FT
GPM
P FT
GPM
P FT
504A 25 1.1 34 100 11.3 8 42 2.7 28 1.4 N/A N/A
754A 32 1.8 39 100 13.8 13 63 6.0 42 2.9 32 1.8
1104A 47 4.3 39 113 18.6 16 92 13.3 62 6.7 47 4.3
1504A 65 8.4 39 113 22.2 22 N/A N/A 84 13.3 65 8.4
2004A 86 16.7 39 113 27.2 30 N/A N/A 112 26.9 86 16.7
CATEGORY I*
WATER HEATERS
(TYPE WH)
MVB
Model
Flow Rates
Minimum Flow Maximum Flow
GPM
P FT T °F
GPM
P FT T °F
504A 29 1.4 29 100 11.3 8
754A 44 2.9 29 100 13.8 13
1104A 61 6.7 29 113 18.6 16
1504A 84 13.3 29 113 22.2 22
2004A 113 27.2 29 113 27.2 29
CATEGORY IV BOILERS
& WATER HEATERS
(TYPE H & WH)
MVB
Model
Flow Rates Pressure Drops
Minimum Flow Maximum Flow 20°F 30°F 39°F
GPM
P FT T °F
GPM
P FT T °F
GPM
P FT
GPM
P FT
GPM
P FT
503A
25
1.1 35 100 11.3 9 43 2.8 29 1.4 N/A N/A
753A
33
1.9 40 100 13.8 13 65 6.4 43 3.1 33 1.9
1003A
43
3.7 40 113 18.6 15 87 12.0 58 6.0 45 3.8
1253A
54
6.2 40 113 22.2 19 109 20.9 73 10.2 56 6.5
1503A
65
9.5 40 113 25.5 23 N/A N/A 87 16.0 67 10.0
1753A
76
13.4 40 113 27.2 27 N/A N/A 101 22.5 78 14.0
2003A
87
15.2 40 116 30.2 30 N/A N/A 116 31.9 89 19.8
2503
120
4.7 35 264 15.7 16 213 11.7 142 6.2 N/A N/A
3003
131
6.3 39 264 23.1 19 255 21.7 170 10.3 131 6.3
3503
153
9.1 39 264 26.8 23 N/A N/A 198 15.2 153 9.1
4003
174
13.5 39 264 33.5 26 N/A N/A 227 23.7 174 13.5
7
*Category I with vertical vent, category III with horizontal venting and no extractor.
‡ Use 30° column as minimum flow for hot water supply.
Boiler Only
Raypak Leadership in Boiler Management
The new modulating or stagefire VERSA IC
TM
fully integrates temperature
control, ignition, safety, temperature safety and individual fault monitoring.
Field upgradable. Raypak’s unique Cold Water Protection control function
is now built in; simply add the appropriate 3-way valve or variable speed
pump. A Modbus communications port is standard for continuous monitor-
ing, trending, and trouble shooting.
BACnet
®
,Metasys
®
Modbus
®
gateway module
(optional)
LONworks
®
gateway module
(optional)
Cascade up to 4 boilers
Modbus RTU comm port standard
All faults and interlocks monitored and reported in plain English
Building Management System integration via optional gateways
BACnet MS/TP, BACnet IP, N2 Metasys or Modbus TCP
LONworks