TempTracker mod+ & TempTracker mod+ Extension Installation Manual 9
WIRING
WIRING THE POWER (TERMINALS 1, 2)
Bring the 120VAC 60Hz power wires through the bottom Knockout of the enclosure.
Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.
Connect the hot line to terminal marked L.
Connect the neutral line to the terminal marked N.
Raypak recommends installing a surge suppressor on the power source to the TempTracker mod+.
WARNING
Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.
Raypak recommends installing a surge suppressor on the power source to the TempTracker mod+.
Mini-MOD
SYSTEM
A
B
C
D
Full Modulation Sequencing Control
1
2
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3
4
5
6
7
8
9
10
11
12
13
15
14
17
16
18
22
20
19
21
24
23
29
25
27
26
28
32
30
31
L
N
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
------
Line
Neutral
120VAC
Power Source
Outdoor Sensor
Sensor Shiled
29
25
27
26
28
32
30
31
T
T
O
O
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
System Sensor
Sensor Shiled
Shutdown,
T-Stat, or
Setback Signal
3
4
5
6
7
8
9
10
11
12
SYS
A
B
C
D
System Pump
or Pump Starter
Boiler Enable
Output
Boiler
Boiler 4-20mA
Modulation Output
4-20mA
Burner
Motor
-
+
Boiler Voltage
Modulation Output
Voltage
Burner
Motor
GND
V+
PROVE
/DHW
SHUTDOWN
/SETBACK
PROVE
/DHW
29
25
27
26
28
32
30
31
T
T
O
O
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
Prove Signal
PROVE
/DHW
29
25
27
26
28
32
30
31
T
T
O
O
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
DHW Signal
PROVE
/DHW
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 30VA MAX
INPUT RATINGS:
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
CAUTION: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
L
N
/TSTAT
SHUTDOWN
/SETBACK
/TSTAT
SHUTDOWN
/SETBACK
/TSTAT
SHUTDOWN
/SETBACK
/TSTAT
WIRING THE SENSORS
WARNING
Connect the shield at the control terminal end and cut the shield wire at the sensor end.
Mini-MOD
SYSTEM
A
B
C
D
Full Modulation Sequencing Control
1
2
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3
4
5
6
7
8
9
10
11
12
13
15
14
17
16
18
22
20
19
21
24
23
29
25
27
26
28
32
30
31
L
N
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
------
Line
Neutral
120VAC
Power Source
Outdoor Sensor
Sensor Shiled
29
25
27
26
28
32
30
31
T
T
O
O
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
System Sensor
Sensor Shiled
Shutdown,
T-Stat, or
Setback Signal
3
4
5
6
7
8
9
10
11
12
SYS
A
B
C
D
System Pump
or Pump Starter
Boiler Enable
Output
Boiler
Boiler 4-20mA
Modulation Output
4-20mA
Burner
Motor
-
+
Boiler Voltage
Modulation Output
Voltage
Burner
Motor
GND
V+
PROVE
/DHW
SHUTDOWN
/SETBACK
PROVE
/DHW
29
25
27
26
28
32
30
31
T
T
O
O
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
Prove Signal
PROVE
/DHW
29
25
27
26
28
32
30
31
T
T
O
O
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
DHW Signal
PROVE
/DHW
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 30VA MAX
INPUT RATINGS:
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
CAUTION: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
L
N
/TSTAT
SHUTDOWN
/SETBACK
/TSTAT
SHUTDOWN
/SETBACK
/TSTAT
SHUTDOWN
/SETBACK
/TSTAT
SYSTEM SENSOR WIRING (TERMINALS 27, 28)
A TempTracker mod+ must be connected to a temperature sensor located in the common header.
The TempTracker mod+ is designed to be connected to a temperature sensor for immersion in a 3/8ID well.
Temperature sensor wires can be extended up to 500’ by splicing shielded 2-conductor cable (Belden #8760 or
equivalent).
Temperature sensors have no polarity. Connect the two wires from the sensor to the TempTracker mod+ terminals
marked SYSTEM TEMP 27, 28.
Connect the sensor shield to the circled terminal 28 with one of the sensor wires.
OUTDOOR SENSOR WIRING (TERMINALS 25, 26)
The TempTracker mod+ will vary the system Set Point when Outdoor Reset is selected based on outdoor
temperature.
Whether in Set Point or Outdoor Reset modes, the outdoor sensor can be used as an Outdoor Cutoff. The
TempTracker mod+ will disable all Boilers when the outdoor temperature is above the adjustable Outdoor Cutoff
temperature. This feature will automatically be activated when an outdoor sensor is connected.
For an outdoor sensor use a Raypak outdoor sensor.
The sensor wires can be extended up to 500’ using shielded 2-conductor cable (Belden #8760 or equivalent).
Temperature sensors have no polarity. Connect the wires from the outdoor sensor to the TempTracker mod+
terminals marked OUTDOOR TEMP - 25, 26.
Connect the shield to the circled terminal 26 with one of the sensor wires.
Mini-MOD
SYSTEM
A
B
C
D
Full Modulation Sequencing Control
1
2
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3
4
5
6
7
8
9
10
11
12
13
15
14
17
16
18
22
20
19
21
24
23
29
25
27
26
28
32
30
31
L
N
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
------
Line
Neutral
120VAC
Power Source
Outdoor Sensor
Sensor Shiled
29
25
27
26
28
32
30
31
T
T
O
O
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
System Sensor
Sensor Shiled
Shutdown,
T-Stat, or
Setback Signal
3
4
5
6
7
8
9
10
11
12
SYS
A
B
C
D
System Pump
or Pump Starter
Boiler Enable
Output
Boiler
Boiler 4-20mA
Modulation Output
4-20mA
Burner
Motor
-
+
Boiler Voltage
Modulation Output
Voltage
Burner
Motor
GND
V+
PROVE
/DHW
SHUTDOWN
/SETBACK
PROVE
/DHW
29
25
27
26
28
32
30
31
T
T
O
O
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
Prove Signal
PROVE
/DHW
29
25
27
26
28
32
30
31
T
T
O
O
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
DHW Signal
PROVE
/DHW
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 30VA MAX
INPUT RATINGS:
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
CAUTION: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
L
N
/TSTAT
SHUTDOWN
/SETBACK
/TSTAT
SHUTDOWN
/SETBACK
/TSTAT
SHUTDOWN
/SETBACK
/TSTAT
WIRING THE SHUTDOWN, TSTAT, OR SETBACK (TERMINALS 31, 32)
The Shutdown will be available when selected as the Shutdown/Tstat/Setback mode from the Startup menu. See
page 15. This will provide the user with a customizable Day/Night Schedule. See page 21.
The Shutdown feature can be used whenever it is desirable to turn off the TempTracker mod+ stage outputs from
a remote location or another controller (i.e. EMS input).
The Tstat option, when selected from the Shutdown/Tstat/Setback startup menu, provide the capability of
controlling the operation of the TempTracker mod+ based on a thermostat input. See page 15. This will provide
the user with a customizable Day/Night Schedule. See page 21.
The thermostat will provide the TempTracker mod+ with a call for heat by shorting terminals 31 and 32.
When the Shutdown input is enabled by closing the dry contact, or when the Tstat input is disabled by opening the
dry-contact, all active boilers will immediately modulate down to low for the Soft-Off period, then turn off.
The System Output relay will remain active until the System Run-On Delay expires and then it will turn off.
Mini-MOD
SYSTEM
A
B
C
D
Full Modulation Sequencing Control
1
2
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3
4
5
6
7
8
9
10
11
12
13
15
14
17
16
18
22
20
19
21
24
23
29
25
27
26
28
32
30
31
L
N
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
------
Line
Neutral
120VAC
Power Source
Outdoor Sensor
Sensor Shiled
29
25
27
26
28
32
30
31
T
T
O
O
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
System Sensor
Sensor Shiled
Shutdown,
T-Stat, or
Setback Signal
3
4
5
6
7
8
9
10
11
12
SYS
A
B
C
D
System Pump
or Pump Starter
Boiler Enable
Output
Boiler
Boiler 4-20mA
Modulation Output
4-20mA
Burner
Motor
-
+
Boiler Voltage
Modulation Output
Voltage
Burner
Motor
GND
V+
PROVE
/DHW
SHUTDOWN
/SETBACK
PROVE
/DHW
29
25
27
26
28
32
30
31
T
T
O
O
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
Prove Signal
PROVE
/DHW
29
25
27
26
28
32
30
31
T
T
O
O
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
DHW Signal
PROVE
/DHW
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 30VA MAX
INPUT RATINGS:
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
CAUTION: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
L
N
/TSTAT
SHUTDOWN
/SETBACK
/TSTAT
SHUTDOWN
/SETBACK
/TSTAT
SHUTDOWN
/SETBACK
/TSTAT
When Setback is selected in the Startup, a BMS/EMS or external clock can provide a Setback signal using these input terminals.
The signal must be a dry contact only. No voltage can be placed across the SHUTDOWN/SETBACK terminals.
Bring the two wires from the dry contact to the terminals marked SHUTDOWN/SETBACK- 31,32.