51
burners should reignite after pre-purge time delay.
8. Test limit control: While burner is operating, move
indicator on high limit control below actual boiler
water temperature. Burner should go off while
blower circulator continues to operate. Raise set-
ting on limit control above boiler water
temperature and burner should reignite after pre-
purge time delay.
9. Test ignition system safety device:
Turn power off.
Close the pilot manual valve.
Turn power on; after about 45 seconds of pre-
purge, the pilot comes on. The pilot (and
therefore the burner) should fail to light. The
standard lockout time is 90 seconds; then the
pilot light goes off and the boiler goes into
post-purge. (If the lockout module is attached
to boiler, a lockout light comes on.)
Turn the power off; open the pilot manual
valve; (reset the lockout module if applicable).
Wait 30 seconds, then turn power on. The
burner should ignite after pre-purge time
delay.
10. To restart system, follow the lighting instructions.
11. High limit control set to design temperature
requirements of system? For multiple zones: flow
adjusted as required in each zone?
12. Boiler cycled with thermostat? Raise to highest
setting and verify boiler goes through normal start-
up cycle. Reduce to lowest setting and verify boiler
goes off.
13. Observed several operating cycles for proper
operation?
14. Set room thermostat or tankstat to desired temper-
ature?
15. Reviewed all instructions shipped with this boiler
with owner or maintenance personnel, returned to
envelope and given to owner or placed in pocket
inside front panel on boiler?
OPERATION
Operating Instructions
Lighting Instructions:
1. STOP! Read the safety information first.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device
which automatically lights the burner. DO NOT try
to light the burner by hand.
5. Remove upper front panel.
6. Turn on main manual gas valve and pilot manual
gas valve.
7. Wait five (5) minutes to clear out any gas. Then
smell for gas, especially near the floor. If you then
smell gas. STOP! Follow the steps in the safety
information. If you do not smell gas, go to next
step.
8. Turn on all electric power to the appliance.
9. Set thermostat to desired setting. The appliance
will operate. The pilot burner will light after the pre-
purge time delay (45 seconds). Then the pilot will
light the main burner.
10. If the appliance will not operate, follow the instruc-
tion "To Turn Off Gas to Appliance", and contact a
qualified service technician.
11. Replace upper front panel.
To Turn Off Gas to Appliance
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if serv-
ice is to be performed.
3. Remove upper front panel.
4. Turn off main manual gas valve and manual pilot
gas valve.
5. Replace access panel.
If boiler fails to start, check for:
Loose connections, blown fuse or service
switch off?
High temperature limit switch set below boiler
water temperature?
Thermostat set below room temperature?
Gas not turned on at meter or boiler?
Incoming dynamic gas pressure less than 6 in.
WC for Natural gas, 10 in. WC for Propane?
MAINTENANCE
Suggested Minimum
Maintenance Schedule:
Regular service by a qualified service agency and
maintenance must be performed to ensure maximum
boiler operating efficiency.
Maintenance as outlined below may be performed by
the owner.
Yearly (Beginning of each heating
season):
1. Annual service call by qualified service agency.
2. Visually check top of vent for soot. Call service
person to clean. Some sediment at bottom of vent
is normal.