SECTION K CONDENSATE DRAIN
WARNING: All condensation should be disposed of according to local, county, state, and federal laws. Refer to
NFGC, section 7.9, for additional information.
The Condensing Heat Exchanger (CHX) can generate up to 1 (one) gallon per hour (GPH) of condensate for every 100,000
BTUH. The maximum condensation rates for different size units are 5 GPH, 7.5 GPH, and 10 GPH for the ADB-500, 750,
and 1000, respectively.
Figure K-1
CONDENSATE TRAP ALIGNMENT