Communication (RS485) Wiring
Required for Optional Slave
Unit(s)
Y-304 Slave Cable Installation from
System Control Module
Y-304 slave cable or equivalent shielded commu-
nications cable (Belden #9842, Belden #8132 or
Alpha 3492C) must be used. Maximum cable
length 100 ft. Correct polarity must be observed.
Make use of wire color coding to ensure polarity.
The shielding [foil wrapper-bare wire (drain)]
MUST be grounded. Grounding is done at the
Master Y-200 Control only. DO NOT ground the
shield at the slave unit end of the cable.
Note: Equivalent shielded cable must be suitable
for RS485 communication applications; must have
100-140 ohm impedance and less than 30 pico-
farad per foot capacitance.
Must be installed in conduit that does not contain
any other wiring.
Port J18 (see Fig. 4) is used for the interconnec-
tion between the master controller and slave units.
Master/Slave interconnection should be wired
from Master to Slave #1, Slave #1 to Slave #2,
Slave #2 to Slave #3, and Slave #3 to Slave #4.
Air Temperature Sensor
Installation
Locate the sensor on the coldest side of building,
usually the north side.
Install the sensor in a shaded area, out of direct
sunlight.
Locate no higher than 2/3 way up the side of the
building, or between the 2nd and 3rd floor if the
building is more than 3 stories tall.
Do not locate under an overhang, near wall cor-
ners, near drafts from stacks, air moving devices,
windows, doors, or balconies.
Shielded twisted pair (18 AWG) must be used for
sensor connections. Polarity must be observed.
Cable length shall not exceed 300 feet, and the
shielding must be grounded.
Grounding is done at the Master Y-200 control
ONLY. Do Not ground the Slave units or
Temperature Sensor enclosure.
Must be installed with properly-sized conduit that
contains no other wiring.
The outdoor air temperature and water tempera-
ture sensor are identical and interchangeable.
Fig. 4: Master RS485 Communications Cable
Schematic
Fig. 5: Typical Outdoor Air Temperature Sensor
Page view 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 39 40