REMOTE CONTROL WIRING
Important Installation Notes for Remote or external wiring configuration
Remote wiring must be run in separate conduit.
Remote wiring must not be run parallel to High Voltage lines.
For runs of under 30 feet, remote wiring should have stranded conductors with a minimum of 22 AWG, 600V,
cable twisting 1.5 to 2.5 and jacketed.
For runs over 30 feet, the conductors should be a minimum of 20 AWG, 600V, cable twisting 1.5 to 2.5 inch lay
that is shielded and jacketed.
Maximum cable length of 200 feet.
For both Two and Three wire remote systems, the provided 7-pin wiring connector must be utilized. Please refer
to the wiring instructions.
1. Turn on power to the heater.
2. Push the mode button to the "POOL" or "SPA" modes
and set the desired temperature.
(example: 80° for Pool and 102°F for Spa)
3. Turn the mode button to "OFF" and remove power from the
heater.
4. On the "Remote Interface Harness" connect the BLUE
wire to one side of the "REMOTE" switch and connect the
ORANGE/BLACK wire for "SPA" operation and the
BLACK/ORANGE wire for the "POOL" operation.
5. Install the "Remote Interface Harness" to the P8 connec-
tor and turn power "ON" to the heater.
See instructions on previous page to activate the
remote control.
1. Turn on power to the heater.
2. Push the mode button to the "POOL" or "SPA" modes
and set the desired temperature. (example:102°F)
3. Turn the mode button to "OFF" and remove power from the
heater.
4. On the "Remote Interface Harness" connect the BLUE
wire to one side of the "REMOTE" switch and connect the
other side to either the ORANGE/BLACK wire for "SPA"
operation or the BLACK/ORANGE wire for "POOL" opera-
tion.
5. Wire nut unused wire on the "Remote Interface Harness".
6. Install the "7-Pin Remote Interface Harness" to the P8
connector and turn power "ON" to the heater.
See instructions on previous page to activate the
remote control.
Note: The remote wires must be connected to the
7-pin connector before it is connected to the board.
3 Wire Remote Control Using Three Position Switch (Pool-Off-Spa, or Low-Off-High)
In this application, it assumed that multiple heating functions are required.
2 Wire Remote Control (On-Off)
In this application, it assumed that only one heating function is required.
Fig# 9492
Fig# 9493